Back to the list

GVWF 326 XSH G / GVWF

Last updated on: Sept. 19, 2025

Information verified by manufacturer

Note on the Completeness of Product Information

The product information listed on this page generally does not include all requested details. Some information may be missing as it is not provided by the manufacturer or depends on the specific configuration of the large heat pump. Especially for products with higher heating capacities, these often involve customized system solutions.


For detailed information, please contact the manufacturer directly.

Information
Product GVWF 326 XSH G
Product Series GVWF
Manufacturer Trane Deutschland GmbH
TRL 9
Max TRL
Operation Mode Heat
Refrigerant R1234ze(E), R515B (R1234ze(E)/ 227ea)
Refrigerant Filling Quantity [kg] 292
Source Type Abwärme (Brine/Water), Geothermie (Brine/Water), Gewässer (Brine/Water), Serverabwärme (Brine/Water)
Sink Type Gebäudewärme, Nahwärme, Prozesswärme
Lifespan [y]
Notes
Comment
Information Source None
Verified True
Technical Specifications
Circuit Type Closed
Number of Circuits 2
Circuit Configuration
Additional Circuit Information
Minimum nominal thermal Capacity [kW] 452
Nominal Thermal Capacity [kW] 1,129
Nominal Electrical Power [kW]
Electrical Connection Voltage [V] 400
Electrical Connection Phase 3
Electrical Connection Frequency [Hz] 50
Temperature Specifications
Minimum Flow Temperature [°C] 5
Maximum Flow Temperature [°C] 65
Minimum Source Temperature [°C] 7
Maximum Source Temperature [°C] 35
Maximum Temperature Increase [K] 55
More information regarding COPs
Physical Dimensions
Length [mm] 4,718
Width [mm] 1,710
Height [mm] 2,032
Weight [kg] 4,297
Maximum Weight [kg] 4,683
Weight Description Transportgewicht / Betriebsgewicht
Condenser Inlet DN125
Condenser Outlet DN115
Evaporator Inlet DN150
Evaporator Outlet DN150
Installation Type Innenaufstellung, Containerlösung möglich
Space Requirements [m2]
Room Height Requirements [mm]
Compressor information
Compressor Turboverdichter
Number of Compressors 3
Compressor Regulation Drehzahlgeregelt
Minmum Load [%] 40
Sound information
Sound Power Level [dB] 97
Sound Pressure Level (1m) [dB]
Sound Pressure Level (10m) [dB] 77

Data provided by the Portal for Large-Scale Heat Pumps © 2025 by Fraunhofer IEG is licensed under CC BY 4.0